B Protocols TAC Xenta Server – Gateway, Technical Manual
158 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
B.6 BACnet PTP (Point To Point)
The Xenta 913 can be configured to connect to a target network through
a BACnet PTP half router to allow monitoring and control of one or
more devices through an I/NET or LON control system.
A number of BACnet Objects can be connected to a corresponding set
of LON Network Variables or I/Net Points to allow one or more target
devices to be monitored and controlled. The target devices can be con-
nected to the router using another type of BACnet protocol such as
MS/TP or IP, or through any other type of network supported by the
router and target devices.
Fig. B.6: BACnet PTP
Value exchange
BACnet or other Network
Device Device Device
RS-232 A
BACnet PTP
LON or I/NET Control System
Xenta 913