MicroNet mn100 Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para TVs e monitores MicroNet mn100. MNL - Control Services Inc. Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 4
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
TAC I/A Series
1
SPECIFICATIONS
HARDWARE
Dimensions
4.37 in. W x 4.29 in. H x 2.00 in. D
(109 mm x 111 mm x 51 mm)
Enclosure
Conforms to NEMA-1 requirements.
Meets UL94-5V flammability for plenum application
use.
Conduit Knockouts
Not applicable. Order optional MicroNet Enclosure,
MNA-FLO-1, if wiring to flexible conduit is desired.
Mounting
35 mm DIN rail or panel.
Wiring Terminals
Screw terminals. Each terminal accepts one AWG
#16 to #24 (1.31 to 0.205 mm
2
maximum) wire.
ELECTRICAL
Power Supply Input
20.4 to 30 Vac, 50/60 Hz.
Maximum Power Consumption
15 VA at 24 Vac, 50/60 Hz, excluding relay output
power.
Surge Immunity Compliance
IEEE C62.41 (IEEE-587, Category A & B).
ENVIRONMENT
Operating Temperature
-40 to 140 °F (-40 to 60 °C)
Shipping and Storage Temperature
-40 to 160 °F (-40 to 71 °C)
Humidity
5 to 95% RH, non-condensing
MNL-100, MNL-150, MNL-200 Series Controllers
I/A Series Micronet MNL-100, MNL-150, MNL-200
The TAC I/A Series™ MicroNet™ MNL-100,
MNL-150, and MNL-200 Series Controllers are
interoperable controllers designed in accordance
with L
o n Ma r k ™ guidelines. When programmed
using WorkPlace Tech Tool, or loaded with a pre-
engineered application, these controllers provide
control for packaged rooftops, heat pumps, fan coils,
unit ventilators, and similar applications.
Controllers feature Sensor Link (S-Link) support, LED
indication, screw terminal blocks, as well as DIN rail
or panel mounting ability.
The MNL-100, MNL-150, and MNL-200 series
controllers use the same physical packaging, but
differ in the type and number of onboard I/O points
they provide.
Stand Alone or Connected
These controllers can function in either standalone
mode or as part of a L
o n Wo r k s ™ TP/FT-10 Free
Topology communications network. Using a TAC
I/A Series MicroNet Sensor (MN-Sx series), the
operator can monitor controller performance and edit
operational values. The WorkPlace Tech Tool software
is used to program the controllers.
AGENCY LISTINGS
US
FCC Part 15, Class A
UL 916, File #E71385 Category PAZX
Canadian
UL Listed to Canadian Safety Standards (CAN/
CSA 22.2)
Australian
Meets requirements to bear the C-Tick Mark
European Community
EMC Directive 89/336/EEC, EN61326
INPUTS AND OUTPUTS
Digital Inputs
(MN 100 and MN 200 only) Dry Contact. Detection of
closed switch requires less than 300 ohm. Detection
of open switch requires more than 100K ohm.
Digital Outputs
Current Ratings
24 VA at 24 Vac, pilot duty.
Specifications continued on next page.
Vista de página 0
1 2 3 4

Resumo do Conteúdo

Página 1 - SPECIFICATIONS

TAC I/A Series1SPECIFICATIONSHARDWAREDimensions4.37 in. W x 4.29 in. H x 2.00 in. D(109 mm x 111 mm x 51 mm)EnclosureConforms to NEMA-1 requirements.M

Página 2 - FEATURES

2TAC I/A SeriesMNL-100, MNL-150, and MNL-200 Series ControllersSchneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, U

Página 3

3TAC I/A SeriesMNL-100, MNL-150, and MNL-200 Series ControllersSchneider Electric 1354 Clifford Avenue, P.O. Box 2940, Loves Park, IL 61132-2940, U

Página 4 - ARCHITECTURE

4TAC I/A SeriesOn October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual ide

Comentários a estes Manuais

Sem comentários